“never plug extension cords into extension cords” is probably the most common piece of electrical related advice I’ve ever heard. But if you have, say, 2 x 2m long extension cords, and you plug one into the other, why is that considered a lot more unsafe than just using a single 4 or 5 meter cord?

Does it just boil down to that extra connection creating another opportunity for the prongs to slip out and cause a spark or short circuit? Or is there something else happening there?

For that matter - why aren’t super long extension cords (50 or more meters) considered unsafe? Does that also just come down to a matter of only having 2 connections versus 4 or more on a daisy chained cord?

Followup stupid question: is whatever causes piggybacked extension cords to be considered unsafe actually that dangerous, or is it the sort of thing that gets parroted around and misconstrued/blown out of proportion? On a scale from “smoking 20 packs of cigarettes a day” to “stubbing your toe on a really heavy piece of furniture”, how dangerous would you subjectively rate daisy chaining extension cords, assuming it was only 1 hop (2 extension cords, no more), and was kept under 5 or 10 metres?

I’m sure there’s probably somebody bashing their head against a wall at these questions, but I’m not trying to be ignorant, I’m just curious. Thank you for tolerating my stupid questions

  • kevincox
    link
    fedilink
    arrow-up
    4
    ·
    1 day ago

    Yeah, there are two components here

    1. Adding extra length.
    2. Adding more outlets.

    2 is the main problem, but you need a little of 1 to have it fail in an unsafe way (ie. not just tripping the circuit breaker).

    If you just add a lot of extra outlets and plug lots of stuff in then you will simply trip the circuit breaker. (Assuming that everything is properly set up according to code.) In order to create a problem you need some extra wiring that is rated for less load than the wall wiring. (Now in practice every splitter has some amount of wiring, so these can be the same device, but most power bars are rated to be “fully used” or have a fuse internally). So the problem looks something like this:

    1. Have a 20A wall circuit.
    2. Plug a 10A extension cord into it.
    3. Plug a power bar or other splitter into the extension cord.
    4. Put enough devices into the splitter to generate 15A of current.

    Now you are overloading the extension cord and risking fire.